Grazing the trickle vent calculation for facades
The table below matches the free-field sound reduction requirements of the building facade to the minimum sound reduction index of the windows and trickle vents. Results are provided in the format:
Window Rw / Trickle Vent Dnew
| Reduction Rw | Window of 2 m^2 (Win/Vent) | Window of 4 m^2 (Win/Vent) | Window of 6 m^2 (Win/Vent) | Window of 8 m^2 (Win/Vent) | Window of 10 m^2 (Win/Vent) |
|---|---|---|---|---|---|
| 16 | 14/20 | 15/21 | 16/22 | 17/23 | 17/23 |
| 17 | 15/21 | 16/22 | 17/23 | 18/24 | 18/24 |
| 18 | 16/22 | 17/23 | 18/24 | 19/25 | 19/25 |
| 19 | 17/23 | 18/24 | 19/25 | 20/26 | 20/26 |
| 20 | 18/24 | 19/25 | 20/26 | 21/27 | 21/27 |
| 21 | 19/25 | 20/26 | 21/27 | 22/28 | 22/28 |
| 22 | 20/26 | 21/27 | 22/28 | 23/29 | 23/29 |
| 23 | 21/27 | 22/28 | 23/29 | 24/30 | 24/30 |
| 24 | 22/28 | 23/29 | 24/30 | 25/31 | 25/31 |
| 25 | 23/29 | 24/30 | 25/31 | 26/32 | 26/32 |
| 26 | 24/30 | 25/31 | 26/32 | 27/33 | 27/33 |
| 27 | 25/31 | 26/32 | 27/33 | 28/34 | 28/34 |
| 28 | 26/32 | 27/33 | 28/34 | 29/35 | 29/35 |
| 29 | 27/33 | 28/34 | 29/35 | 30/36 | 30/36 |
| 30 | 28/34 | 29/35 | 30/36 | 31/37 | 31/37 |
| 31 | 29/35 | 30/36 | 31/37 | 32/38 | 32/38 |
| 32 | 30/36 | 31/37 | 32/38 | 33/39 | 33/39 |
| 33 | 31/37 | 32/38 | 33/39 | 34/40 | 34/40 |
| 34 | 32/38 | 33/39 | 34/40 | 35/41 | 35/41 |
| 35 | 33/39 | 34/40 | 35/41 | 36/42 | 36/42 |
| 36 | 34/40 | 35/41 | 36/42 | 37/43 | 37/43 |
| 37 | 35/41 | 36/42 | 37/43 | 38/44 | 38/44 |
| 38 | 36/42 | 37/43 | 38/44 | 39/45 | 39/45 |
| 39 | 37/43 | 38/44 | 39/45 | 40/46 | 40/46 |
| 40 | 38/44 | 39/45 | 40/46 | 41/47 | 41/47 |
| 41 | 39/45 | 40/46 | 41/47 | 42/48 | 42/48 |
| 42 | 40/46 | 41/47 | 42/48 | 43/49 | 43/49 |
| 43 | 41/47 | 42/48 | 43/49 | 44/50 | 44/50 |
| 44 | 42/48 | 43/49 | 44/50 | 45/51 | 45/51 |
| 45 | 43/49 | 44/50 | 45/51 | 46/52 | 46/52 |